We are a newly renovated  (4-2004 thru 10-2005)extended aeration plant (VLR) which consists of a inline grinder (muffin monster) a raw pumping station, a fine screen and aerated grit removal. The biological treatment consists of (two) Vertical Loop Reactors ran in series followed by secondary clarifiers (two 50' circular clarifers). We disinfect by using a Trojan-3000 Plus Ultra Violet light system. Our design flow is 1.5mgd with a peak of 3.0mgd. 
 
Waste Water Plant

Edinburgh Wast Water Plant

Our NPDES effluent limitations are 25 and 40 on CBOD, and 30 and 45 on S.S. Ammonia limits are 10.4 mg/l and D.O. minimal is 3 mg/l. We discharge directly into the Big Blue River.
 
Since we went online with our VLR's our average CBOD is less than 1mg/l and our S.S. is usually around 2-4mg/l and ammonia less than .1mg/l. We are acheiving 99% removal on CBOD 98% removal on S.S. and 99% removal on ammonia.
 
 
 